PVC - Polyvinyl Chloride Pipes - Supports
Maximum distance between PVC - Polyvinyl Chloride - pipes supports depends on operating temperature:
PVC Pipe - Schedule 40
| NPS (inches) | Maximum Support Spacing (feet) | ||
|---|---|---|---|
| Operating Temperature (oF) | |||
| 60 | 100 | 140 | |
| 1/2 | 4.5 | 4 | 2.5 |
| 3/4 | 5 | 4 | 2.5 |
| 1 | 5.5 | 4.5 | 2.5 |
| 1 1/4 | 5.5 | 5 | 3 |
| 1 1/2 | 6 | 5 | 3 |
| 2 | 6 | 5 | 3 |
| 3 | 7 | 6 | 3.5 |
| 4 | 7.5 | 6.5 | 4 |
| 6 | 8.5 | 7.5 | 4.5 |
| 8 | 9 | 8 | 4.5 |
PVC Pipe - Schedule 80
| NPS (inches) | Maximum Support Spacing (feet) | ||
|---|---|---|---|
| Operating Temperature (oF) | |||
| 60 | 100 | 140 | |
| 1/2 | 5 | 4.5 | 2.5 |
| 3/4 | 5.5 | 4.5 | 2.5 |
| 1 | 6 | 5 | 3 |
| 1 1/2 | 6.5 | 5.5 | 3.5 |
| 2 | 7 | 6 | 3.5 |
| 3 | 8 | 7 | 4 |
| 4 | 9 | 7.5 | 4.5 |
| 6 | 10 | 9 | 5 |
| 8 | 11 | 9.5 | 5.5 |
- 1 ft (foot) = 0.3048 m
- T (oC) = 5/9 (T (oF) - 32)
Related Topics
• Dimensions of Pipes and Tubes
Pipe, tube and fittings sizes and dimensions. Inside and outside diameters, weights and more.
Related Documents
ASTM D2241 - Poly(Vinyl Chloride) (PVC) Pressure-Rated Pipe (SDR Series) - Dimensions
Dimensions of PVC pipe SDR series.
ASTM D2665 - Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Drain, Waste, and Vent Pipe and Fittings - Dimensions
PVC drain, waste, and vent pipe dimensions.
ASTM D2729 - Poly(Vinyl Chloride) (PVC) Sewer Pipe - Dimensions
Dimensions of Poly(Vinyl Chloride) (PVC) Sewer Pipes with belled end.
ASTM D2846 - CPVC Plastic Hot and Cold Water Distribution Tubes - Dimensions
Dimensions of CTS - Copper Tube Sized CPVC (Chlorinated Poly Vinyl Chloride) tubes.
ASTM D3034 PSM PVC Sewer PIpe - Dimensions
Dimensions of PSM PVC sewer pipe.
EN 1329 - PVC Piping for Soil and Waste Discharge - Dimensions
Dimensions of PVC pipes according EN 1329.
EN 1452 - Unplasticized Poly Vinyl Chloride (PVC-U) - Dimensions
Dimensions of PVC-U pipe according EN 1452.
EN 1453 - PVC Piping with Structured Walls - Dimensions
Dimensions of PVC pipes with structured walls according EN 1453.
Horizontal Pipe Hanger Supports - Spacing and Rod Size
Recommended maximum support span between hangers - and rod sizes for straight horizontal pipes.
ISO 11922 - Thermoplastics Pipes for the Conveyance of Fluids - Dimensions
Dimensions of plastic pipes according ISO 11922 - metric and imperial units.
ISO 161 - Thermoplastics Pipes - Dimensions
Dimensions of thermoplastic pipes according ISO 161.
PP - PolyPropylene Pipes - Support Spacing
Maximum distance between PolyPropylene pipes supports.
Pressfit Pipes - Supports
Maximum distance between pressfit pipe supports.
PVC Pipes - Equivalent Length and Pressure Loss in Fittings
Minor loss in PVC and CPVC fittings expressed as equivalent length of straight pipe.
PVC Pipes Schedule 40 - Friction Loss vs. Water Flow
Water flow in thermoplastic PVC and CPVC pipes Schedule 40 - friction loss (ft/100 ft, psi/100 ft) and flow velocities at dimensions ranging 1/2 to 16 inches.
PVC Pipes Schedule 40 - Friction Loss vs. Water Flow Diagrams
Friction loss (psi/100 ft) and velocity for water flow in plastic PVC pipe schedule 40.
PVC Pipes Schedule 80 - Friction Loss vs. Water Flow
Water flow in thermoplastic PVC and CPVC pipes Schedule 80 - friction loss (ft/100 ft, psi/100 ft) and flow velocities at dimensions ranging 1/2 to 16 inches.
Thermoplastic Pipes - Support Distance vs. Temperature
Maximum space between supports for PVC, CPVC, PVDF and PP pipes vs. temperature.