PVC Pipes Schedule 40 - Friction Loss vs. Water Flow

Sponsored Links

Friction loss and flow velocities in PVC and CPVC pipes Schedule 40 with water are indicated in the table below. The table can be used for pipes in other thermoplastic materials where the inner diameter corresponds to PVC Pipe
Schedule 40
.

  • 1 ft (foot) = 0.3048 m
  • 1 ft/s = 0.3048 m/s
  • 1 gal (US)/min =6.30888x10-5 m3/s = 0.227 m3/h = 0.0631 dm3(liter)/s = 2.228x10-3 ft3/s = 0.1337 ft3/min
  • 1 psi/100 ft = 2.3 ftH2O/100 ft = 2262 mmH2O/100 m = 22.6 kPa/100 m

Note! Velocities should not exceed 5 feet per second.

The values can be used to calculate minor pressure loss with the Equivalent Pipe Length Method.

PVC Pipes Schedule 40 - Friction Loss - 1/2"
Volume Flow
(gal/min)

Volume Flow
(gal/hr)
Velocity
(ft/sec)
Friction Head
(ftH2O/100 ft)

Friction Loss
(psi/100 ft)
1 60 1.1 2.1 0.9
2 120 2.3 4.2 1.8
5 300 5.6 23.4 10.5
7 420 7.9 43.1 18.6
10 600 11.3 82.0 35.5
PVC Pipes Schedule 40 - Friction Loss - 3/4"
Volume Flow
(gal/min)
Volume Flow
(gal/hr)
Velocity
(ft/sec)
Friction Head
(ft/100 ft)
Friction Loss
(psi/100 ft)
1 60 0.6 0.5 0.2
2 120 1.3 1.0 0.4
5 300 3.2 5.7 2.5
7 420 4.4 10.5 4.6
10 600 6.3 20.0 8.7
15 900 9.5 42.5 18.4
20 1200 12.7 72.3 31.3
PVC Pipes Schedule 40 - Friction Loss - 1"
Volume Flow
(gal/min)
Volume Flow
(gal/hr)
Velocity
(ft/sec)
Friction Head
(ft/100 ft)
Friction Loss
(psi/100 ft)
2 120 0.8 0.6 0.2
5 300 1.9 1.7 0.8
7 420 2.7 3.2 1.4
10 600 3.9 6.0 2.6
15 900 5.8 12.8 5.5
20 1200 7.7 21.8 9.4
25 1500 9.7 32.9 14.2
30 1800 11.6 46.1 20.0
PVC Pipes Schedule 40 - Friction Loss - 1 1/4"
Volume Flow
(gal/min)
Volume Flow
(gal/hr)
Velocity
(ft/sec)
Friction Head
(ft/100 ft)
Friction Loss
(psi/100 ft)
2 120 0.4 0.1 0.1
5 300 1.1 0.4 0.2
7 420 1.6 0.8 0.4
10 600 2.2 1.6 0.7
15 900 3.3 3.3 1.4
20 1200 4.4 5.6 2.4
25 1500 5.5 8.5 3.7
30 1800 6.6 11.9 5.1
35 2100 7.7 15.8 6.8
40 2400 8.8 20.2 8.7
45 2700 9.9 25.1 10.9
50 3000 11.1 30.5 13.2
PVC Pipes Schedule 40 - Friction Loss - 1 1/2"
Volume Flow
(gal/min)
Volume Flow
(gal/hr)
Velocity
(ft/sec)
Friction Head
(ft/100 ft)
Friction Loss
(psi/100 ft)
2 120 0.3 0.1 0.03
5 300 0.8 0.2 0.1
7 420 1.1 0.4 0.2
10 600 1.6 0.7 0.3
15 900 2.4 1.5 0.7
20 1200 3.2 2.6 1.1
25 1500 4.0 4.0 1.7
30 1800 4.9 5.5 2.4
35 2100 5.7 7.4 3.2
40 2400 6.5 9.4 4.1
45 2700 7.3 11.7 5.1
50 3000 8.1 14.3 6.2
60 3600 9.7 20.0 8.7
PVC Pipes Schedule 40 - Friction Loss - 2"
Volume Flow
(gal/min)
Volume Flow
(gal/hr)
Velocity
(ft/sec)
Friction Head
(ft/100 ft)
Friction Loss
(psi/100 ft)
5 300 0.5 0.07 0.03
7 420 0.7 0.1 0.05
10 600 1.0 0.2 0.09
15 900 1.5 0.5 0.2
20 1200 2.0 0.8 0.3
25 1500 2.4 1.2 0.5
30 1800 2.9 1.6 0.7
35 2100 3.4 2.2 0.9
40 2400 3.9 2.8 1.2
45 2700 4.4 3.4 1.5
50 3000 4.9 4.2 1.8
60 3600 5.9 5.8 2.5
70 4200 6.8 7.8 3.4
75 4500 7.3 8.8 3.8
80 4800 7.8 9.9 4.3
90 5400 8.8 12.4 5.4
100 6000 9.8 15.0 6.5
PVC Pipes Schedule 40 - Friction Loss - 2 1/2"
Volume Flow
(gal/min)
Volume Flow
(gal/hr)
Velocity
(ft/sec)
Friction Head
(ft/100 ft)
Friction Loss
(psi/100 ft)
5 300 0.3 0.04 0.02
7 420 0.5 0.05 0.02
10 600 0.7 0.1 0.04
15 900 1.0 0.2 0.08
20 1200 1.4 0.3 0.1
25 1500 1.7 0.5 0.2
30 1800 2.1 0.7 0.3
35 2100 2.4 0.9 0.4
40 2400 2.7 1.2 0.5
45 2700 3.1 1.4 0.6
50 3000 3.4 1.8 0.8
60 3600 4.1 2.5 1.1
70 4200 4.8 3.3 1.4
75 4500 5.1 3.7 1.6
80 4800 5.5 4.2 1.8
90 5400 6.2 5.2 2.3
100 6000 6.8 6.3 2.7
125 7500 8.6 9.6 4.2
150 9000 10.3 13.4 5.8
PVC Pipes Schedule 40 - Friction Loss - 3"
Volume Flow
(gal/min)
Volume Flow
(gal/hr)
Velocity
(ft/sec)
Friction Head
(ft/100 ft)
Friction Loss
(psi/100 ft)
5 300 0.2 0.02 0.01
7 420 0.3 0.02 0.01
10 600 0.4 0.03 0.01
15 900 0.7 0.07 0.03
20 1200 0.9 0.1 0.05
25 1500 1.1 0.2 0.07
30 1800 1.3 0.2 0.1
35 2100 1.6 0.3 0.1
40 2400 1.8 0.4 0.2
45 2700 2.0 0.5 0.2
50 3000 2.2 0.6 0.3
60 3600 2.7 0.9 0.4
70 4200 3.1 1.1 0.5
75 4500 3.3 1.3 0.6
80 4800 3.5 1.4 0.6
90 5400 4.0 1.8 0.8
100 6000 4.4 2.2 0.9
125 7500 5.5 3.3 1.4
150 9000 6.6 4.6 2.0
175 10500 7.7 6.2 2.7
200 12000 8.8 7.9 3.4
250 15000 11.0 11.9 5.2
PVC Pipes Schedule 40 - Friction Loss - 4"
Volume Flow
(gal/min)
Volume Flow
(gal/hr)
Velocity
(ft/sec)
Friction Head
(ft/100 ft)
Friction Loss
(psi/100 ft)
20 1200 0.5 0.03 0.01
25 1500 0.6 0.04 0.02
30 1800 0.8 0.06 0.03
35 2100 0.9 0.08 0.04
40 2400 1.0 0.1 0.05
45 2700 1.2 0.1 0.06
50 3000 1.3 0.2 0.07
60 3600 1.5 0.2 0.1
70 4200 1.8 0.3 0.1
75 4500 1.9 0.3 0.2
80 4800 2.1 0.4 0.2
90 5400 2.3 0.5 0.2
100 6000 2.6 0.6 0.3
125 7500 3.2 0.9 0.4
150 9000 3.8 1.2 0.5
175 10500 4.5 1.6 0.7
200 12000 5.1 2.1 0.9
250 15000 6.4 3.2 1.4
300 18000 7.7 4.4 1.9
350 21000 9.0 5.9 2.6
400 24000 10.2 7.5 3.3
PVC Pipes Schedule 40 - Friction Loss - 5"
Volume Flow
(gal/min)
Volume Flow
(gal/hr)
Velocity
(ft/sec)
Friction Head
(ft/100 ft)
Friction Loss
(psi/100 ft)
30 1800 0.5 0.02 0.01
35 2100 0.6 0.03 0.01
40 2400 0.7 0.03 0.01
45 2700 0.7 0.04 0.02
50 3000 0.8 0.05 0.02
60 3600 1.0 0.07 0.03
70 4200 1.1 0.1 0.04
75 4500 1.2 0.1 0.05
80 4800 1.3 0.1 0.06
90 5400 1.5 0.2 0.07
100 6000 1.6 0.2 0.08
125 7500 2.0 0.3 0.1
150 9000 2.4 0.4 0.2
175 10500 2.8 0.5 0.2
200 12000 3.3 0.7 0.3
250 15000 4.1 1.1 0.5
300 18000 4.9 1.5 0.6
350 21000 5.7 2.0 0.9
400 24000 6.5 2.5 1.1
450 27000 7.3 3.1 1.3
500 30000 8.1 3.7 1.6
PVC Pipes Schedule 40 - Friction Loss - 6"
Volume Flow
(gal/min)
Volume Flow
(gal/hr)
Velocity
(ft/sec)
Friction Head
(ft/100 ft)
Friction Loss
(psi/100 ft)
50 3000 0.6 0.02 0.01
60 3600 0.7 0.03 0.01
70 4200 0.8 0.04 0.02
75 4500 0.8 0.05 0.02
80 4800 0.9 0.05 0.02
90 5400 1.0 0.06 0.03
100 6000 1.1 0.08 0.04
125 7500 1.4 0.1 0.05
150 9000 1.7 0.2 0.07
175 10500 2.0 0.2 0.1
200 12000 2.3 0.3 0.1
250 15000 2.8 0.4 0.2
300 18000 3.4 0.6 0.3
350 21000 3.9 0.8 0.3
400 24000 4.5 1.0 0.4
450 27000 5.1 1.3 0.6
500 30000 5.6 1.5 0.7
750 45000 8.4 3.3 1.4
1000 60000 11.2 5.5 2.4
PVC Pipes Schedule 40 - Friction Loss - 8"
Volume Flow
(gal/min)
Volume Flow
(gal/hr)
Velocity
(ft/sec)
Friction Head
(ft/100 ft)
Friction Loss
(psi/100 ft)
100 6000 0.7 0.03 0.01
125 7500 0.8 0.04 0.02
150 9000 1.0 0.04 0.02
175 10500 1.1 0.06 0.02
200 12000 1.3 0.07 0.03
250 15000 1.6 0.1 0.05
300 18000 1.9 0.2 0.07
350 21000 2.3 0.2 0.09
400 24000 2.6 0.3 0.1
450 27000 2.9 0.3 0.1
500 30000 3.2 0.4 0.2
750 45000 4.9 0.9 0.4
1000 60000 6.5 1.5 0.6
1250 75000 8.1 2.2 1.0
1500 90000 9.7 3.1 1.3
PVC Pipes Schedule 40 - Friction Loss - 10"
Volume Flow
(gal/min)
Volume Flow
(gal/hr)
Velocity
(ft/sec)
Friction Head
(ft/100 ft)
Friction Loss
(psi/100 ft)
200 12000 0.8 0.03 0.01
250 15000 1.0 0.04 0.02
300 18000 1.2 0.05 0.02
350 21000 1.4 0.07 0.03
400 24000 1.6 0.09 0.04
450 27000 1.9 0.1 0.05
500 30000 2.1 0.1 0.06
750 45000 3.1 0.3 0.1
1000 60000 4.1 0.5 0.2
1250 75000 5.1 0.7 0.3
1500 90000 6.2 1.0 0.4
2000 120000 8.2 1.7 0.7
2500 150000 10.3 2.6 1.1
PVC Pipes Schedule 40 - Friction Loss - 12"
Volume Flow
(gal/min)
Volume Flow
(gal/hr)
Velocity
(ft/sec)
Friction Head
(ft/100 ft)
Friction Loss
(psi/100 ft)
350 21000 1 0.03 0.01
400 24000 1.2 0.04 0.02
450 27000 1.3 0.05 0.02
500 30000 1.5 0.06 0.03
750 45000 2.2 0.1 0.05
1000 60000 2.9 0.2 0.09
1250 75000 3.6 0.3 0.1
1500 90000 4.3 0.4 0.2
2000 120000 5.8 0.7 0.3
2500 150000 7.2 1.1 0.5
3000 180000 8.7 1.6 0.7
3500 210000 10.1 2.1 0.9
4000 240000 11.1 2.7 1.2
PVC Pipes Schedule 40 - Friction Loss - 14"
Volume Flow
(gal/min)
Volume Flow
(gal/hr)
Velocity
(ft/sec)
Friction Head
(ft/100 ft)
Friction Loss
(psi/100 ft)
500 30000 1.2 0.03 0.01
750 45000 1.8 0.07 0.03
1000 60000 2.4 0.1 0.05
1250 75000 3.0 0.2 0.08
1500 90000 3.6 0.3 0.1
2000 120000 4.7 0.5 0.2
2500 150000 5.9 0.7 0.3
3000 180000 7.1 1.0 0.4
3500 210000 8.3 1.3 0.6
4000 240000 9.5 1.7 0.7
4500 270000 10.7 2.1 0.9
5000 300000 11.9 2.5 1.1
5500 330000 13.1 3.0 1.3
6000 360000 14.2 3.6 1.5
6500 390000 15.4 4.1 1.8
7000 420000 16.6 4.7 2.0
7500 450000 17.8 5.4 2.3
PVC Pipes Schedule 40 - Friction Loss - 16"
Volume Flow
(gal/min)
Volume Flow
(gal/hr)
Velocity
(ft/sec)
Friction Head
(ft/100 ft)
Friction Loss
(psi/100 ft)
500 30000 0.9 0.02 0.01
750 45000 1.4 0.04 0.02
1000 60000 1.8 0.07 0.03
1250 75000 2.3 0.1 0.04
1500 90000 2.7 0.1 0.06
2000 120000 3.6 0.2 0.1
2500 150000 4.5 0.4 0.2
3000 180000 5.5 0.5 0.2
3500 210000 6.4 0.7 0.3
4000 240000 7.3 0.9 0.4
4500 270000 8.2 1.1 0.5
5000 300000 9.1 1.3 0.6
5500 330000 10.0 1.6 0.7
6000 360000 10.9 1.9 0.8
6500 390000 11.8 2.2 0.9
7000 420000 12.7 2.5 1.1
7500 450000 13.6 2.8 1.2
8000 480000 14.5 3.2 1.4
8500 510000 14.4 3.5 1.5
9000 540000 16.5 3.9 1.7
9500 570000 17.3 4.3 1.9
10000 600000 18.2 4.8 2.1

Pressure loss values can be calculated with the Hazen-Williams Equation or the Darcy-Weisbach Formula.

Sponsored Links

Related Topics

Fluid Flow and Pressure Loss

Pipe lines - fluid flow and pressure loss - water, sewer, steel pipes, pvc pipes, copper tubes and more.

Related Documents

ASTM D1785 and ASTM F441 - PVC and CPVC Pipes Schedule 40 & 80

Standard dimensions and weight of PVC - Polyvinyl Chloride - and CPVC - Chlorinated Polyvinyl Chloride.

ASTM D2241 - Poly(Vinyl Chloride) (PVC) Pressure-Rated Pipe (SDR Series) - Dimensions

Dimensions of PVC pipe SDR series.

EN 1452 - Unplasticized Poly Vinyl Chloride (PVC-U) - Dimensions

Dimensions of PVC-U pipe according EN 1452.

Hazen-Williams Friction Loss Equation - calculating Head Loss in Water Pipes

Friction head loss (ftH2O per 100 ft pipe) in water pipes can be estimated with the empirical Hazen-Williams equation.

Hot Water Systems - Equivalent Length vs. Fittings Resistance

Equivalent length of fittings like bends, returns, tees and valves in hot water heating systems - equivalent length in feet and meter.

ISO 11922 - Thermoplastics Pipes for the Conveyance of Fluids - Dimensions

Dimensions of plastic pipes according ISO 11922 - metric and imperial units.

ISO 161 - Thermoplastics Pipes - Dimensions

Dimensions of thermoplastic pipes according ISO 161.

Lined Pipes - Pressure Loss vs. Water Flow

Pressure drop diagrams for PTFE, PP, PFA and PVDF lined pipes.

Plastic Pipes - Friction Head Loss vs. Water Flow

Friction head loss (ft/100 ft) vs. water flow in plastic pipes like PVC, PP, PE or PEH.

Plastic Pipes - Maximum Operating Temperatures

Piping materials like ABS, PE, PVC, CPVC, PB, PP and SR and pressure and operating temperature limits.

PVC - Polyvinyl Chloride Pipes - Supports

Distance between PVC pipe supports.

PVC Pipes - Equivalent Length and Pressure Loss in Fittings

Minor loss in PVC and CPVC fittings expressed as equivalent length of straight pipe.

PVC Pipes - Pressure Ratings vs. Size

Maximum operating and required burst pressure of PVC - Polyvinyl Chloride - pipe fittings.

PVC Pipes - Temperature Expansion Loops

Calculate temperature expansion and contraction in PVC piping systems.

PVC Pipes Schedule 40 - Friction Loss vs. Water Flow Diagrams

Friction loss (psi/100 ft) and velocity for water flow in plastic PVC pipe schedule 40.

PVC Pipes Schedule 80 - Friction Loss vs. Water Flow

Water flow in thermoplastic PVC and CPVC pipes Schedule 80 - friction loss (ft/100 ft, psi/100 ft) and flow velocities at dimensions ranging 1/2 to 16 inches.

PVC, CPVC, Carbon Steel, Stainless Steel and Fiberglass Pipes - Thermal Expansion Diagrams

Thermal expansion of PVC, CPVC, Carbon and Stainless Steel and Fiberglass pipes.

Sponsored Links

Search Engineering ToolBox

  • the most efficient way to navigate the Engineering ToolBox!

SketchUp Extension - Online 3D modeling!

Add standard and customized parametric components - like flange beams, lumbers, piping, stairs and more - to your Sketchup model with the Engineering ToolBox - SketchUp Extension - enabled for use with the amazing, fun and free SketchUp Make and SketchUp Pro . Add the Engineering ToolBox extension to your SketchUp from the Sketchup Extension Warehouse!

Privacy

We don't collect information from our users. Only emails and answers are saved in our archive. Cookies are only used in the browser to improve user experience.

Some of our calculators and applications let you save application data to your local computer. These applications will - due to browser restrictions - send data between your browser and our server. We don't save this data.

Google use cookies for serving our ads and handling visitor statistics. Please read Google Privacy & Terms for more information about how you can control adserving and the information collected.

AddThis use cookies for handling links to social media. Please read AddThis Privacy for more information.