Electrical Enclosure Types by NEMA
For enclosures used in
Non-Hazardous Locations
Type 1 : General Purpose - Indoor
- Enclosures constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment and to provide a degree of protection against falling dirt.
Type 2 : Drip-Proof - Indoor
- Enclosures constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment, to provide a degree of protection against falling dirt, and to provide a degree of protection against dripping and light splashing of liquids.
Type 3 : Dust tight, Rain tight, Sleet tight - Outdoor
- Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment - to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust - and that will be undamaged by the external formation of ice on the enclosure.
Type 3R : Rain tight, Sleet Resistant - Outdoor
- Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment - to provide a degree of protection against falling dirt, rain, sleet, and snow - and that will be undamaged by the external formation of ice on the enclosure.
Type 3S : Dust tight, Rain tight, Sleet tight - Outdoor
- Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment - to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust - and in which the external mechanism(s) remain operable when ice laden.
Type 4 : Watertight, Dust tight, Sleet Resistant - Indoor & - Outdoor
- Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment - to provide a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water, and hose-directed water - and that will be undamaged by the external formation of ice on the enclosure.
Type 4X : Watertight, Dust tight, Corrosion-Resistant - Indoor & - Outdoor
- Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment - to provide a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water, hose-directed water, and corrosion and that will be undamaged by the external formation of ice on the enclosure.
Type 5 : Dust tight, Drip-Proof - Indoor
- Enclosures constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment - to provide a degree of protection against falling dirt - against settling airborne dust, lint, fibers, and flyings - and to provide a degree of protection against dripping and light splashing of liquids.
Type 6 : Occasionally Submersible, Watertight, Sleet Resistant - Indoor & - Outdoor
- Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment - to provide a degree of protection against falling dirt - against hose-directed water and the entry of water during occasional temporary submersion at a limited depth - and that will be undamaged by the external formation of ice on the enclosure.
Type 6P : Watertight, Sleet Resistant Prolonged Submersion - Indoor & - Outdoor
- Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment - to provide a degree of protection against falling dirt - against hose-directed water and the entry of water during prolonged submersion at a limited depth - and that will be undamaged by the external formation of ice on the enclosure.
Type 12 : Dust tight and Drip tight - Indoor
- Enclosures constructed (without knockouts) for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment - to provide a degree of protection against falling dirt - against circulating dust, lint, fibers, and flyings - and against dripping and light splashing of liquids.
Type 12K : Dust tight and Drip tight, with Knockouts - Indoor
- Enclosures constructed (with knockouts) for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment - to provide a degree of protection against falling dirt - against circulating dust, lint, fibers, and flyings - and against dripping and light splashing of liquids.
Type 13 : Oil tight and Dust tight - Indoor
- Enclosures constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment - to provide a degree of protection against falling dirt - against circulating dust, lint, fibers, and flyings - and against the spraying, splashing, and seepage of water, oil, and noncorrosive coolants.
For enclosures used in
Hazardous Locations
Type 7 : Class I, Group A, B, C or D Hazardous Locations - Indoor
- Enclosures constructed for indoor use in hazardous locations classified as Class I, Division 1, Groups A, B, C, or D as defined in NFPA 70.
Type 8 : Class I, Group A, B, C or D Hazardous Location - Indoor & - Outdoor
- Enclosures constructed for either indoor or outdoor use in hazardous locations classified as Class I, Division 1, Groups A, B, C, and D as defined in NFPA 70.
Type 9 : Class II, Group E, F or G Hazardous Locations - Indoor
- Enclosures constructed for indoor use in hazardous locations classified as Class II, Division 1, Groups E, F, or G as defined in NFPA 70.
Type 10 : Requirements of Mine Safety and Health Administration
- Enclosures constructed to meet the requirements of the Mine Safety and Health Administration, 30 CFR, Part 18.
For more detailed and complete information, NEMA Standards Publication 250-2003, Enclosures for Electrical Equipment (1000 Volts Maximum) should be consulted.
Related Topics
• Electrical
Electrical engineering with units, amps and electrical wiring. Wire gauges, electrical formulas, motors and more.
• Risk, Reliability and Safety
Risk, reliability and safety in process control systems.
Related Documents
Chemicals Hazard Rating System
The National Fire Protection Association (NFPA) hazard system for chemical materials.
Electrical Motors - NEMA Frame Assignments
NEMA frame assignments.
Electrical Motors Efficiency Ratings
NEMA - electrical motor efficiency ratings.
NEMA - National Electrical Manufacturers Association
National Electrical Manufacturers Association.
NEMA and IEC Enclosure Classifications
NEMA enclosure classifications versus IEC enclosure classifications.
NEMA Enclosure Standards for Electric Motors
NEMA enclosure standard for electrical motors.
NFPA - National Fire Protection Association
The U.S. authority on fire, electrical and building safety.
Water Sprinkler Protected Areas and Hazard Classification
Maximum fire sprinkler protected area vs. classification and construction.