Electrical Motors - NEMA Frame Assignments
National Electric Manufacturers Association (NEMA) standardized frame assignments for
- single-phase motors horizontal and vertical
- polyphase squirrel-cage motors horizontal and vertical - open time
- polyphase squirrel-cage motors horizontal and vertical - fan-cooled
are indicated below:
Single-phase motors horizontal and vertical
Power (hp) | speed (rpm) | ||
---|---|---|---|
3600 | 1800 | 1200 | |
3/4 | - | - | 145T |
1 | - | 143T | 182T |
1 1/2 | 143T | 145T | 184T |
2 | 145T | 182T | - |
3 | 182T | 184T | - |
5 | 184T | 213T | - |
7 1/2 | 213T | 215T | - |
Polyphase squirrel-cage motors horizontal and vertical - open time
Power (hp) | speed (rpm) | |||
---|---|---|---|---|
3600 | 1800 | 1200 | 900 | |
1/2 | - | - | - | 143T |
3/4 | - | - | 143T | 145T |
1 | - | 143T | 145T | 182T |
1 1/2 | 143T | 145T | 182T | 184T |
2 | 145T | 145T | 184T | 213T |
3 | 145T | 182T | 213T | 215T |
5 | 182T | 184T | 215T | 254T |
7 1/2 | 184T | 213T | 254T | 256T |
10 | 213T | 215T | 256T | 284T |
15 | 215T | 254T | 284T | 286T |
20 | 254T | 256T | 286T | 324T |
25 | 256T | 284T | 324T | 326T |
30 | 284TS | 286T | 326T | 364T |
40 | 286TS | 324T | 364T | 365T |
50 | 324TS | 326T | 365T | 404T |
60 | 326TS | 364TS | 404T | 405T |
75 | 364TS | 365TS | 405T | 444T |
100 | 365TS | 404TS | 444T | 445T |
125 | 404TS | 405TS | 445T | - |
150 | 405TS | 444TS | - | - |
200 | 444TS | 445TS | - | - |
250 | 445TS+ | - | - | - |
Polyphase squirrel-cage motors horizontal and vertical - fan-cooled
Power (hp) | speed (rpm) | |||
---|---|---|---|---|
3600 | 1800 | 1200 | 900 | |
1/2 | - | - | - | 143T |
3/4 | - | - | 143T | 145T |
1 | - | 143T | 145T | 182T |
1 1/2 | 143T | 145T | 182T | 184T |
2 | 145T | 145T | 184T | 213T |
3 | 182T | 182T | 213T | 215T |
5 | 184T | 184T | 215T | 254T |
7 1/2 | 213T | 213T | 254T | 256T |
10 | 215T | 215T | 256T | 284T |
15 | 254T | 254T | 284T | 286T |
20 | 256T | 256T | 286T | 324T |
25 | 284TS | 284T | 324T | 326T |
30 | 286TS | 286T | 326T | 364T |
40 | 324TS | 324T | 364T | 365T |
50 | 326TS | 326T | 365T | 404T |
60 | 364TS | 364TS | 404T | 405T |
75 | 365TS | 365TS | 405T | 444T |
100 | 405TS | 405TS | 444T | 445T |
125 | 444TS | 444TS | 445T | - |
150 | 445TS | 445TS | - | - |
Related Topics
• Electrical
Electrical units, amps and electrical wiring, wire gauge and AWG, electrical formulas and motors.
Related Documents
Electrical Enclosure Types by NEMA
Description of NEMA electrical enclosures types.
Electrical Motors - Frame Dimensions
Electrical motors NEMA frame dimensions.
Electrical Motors Efficiency Ratings
NEMA - electrical motor efficiency ratings.
NEMA - National Electrical Manufacturers Association
National Electrical Manufacturers Association.
NEMA A, B, C and D Electrical Motor Design
NEMA has established the four different designs A, B, C and D for electrical induction motors.
NEMA Enclosure Standards for Electric Motors
NEMA enclosure standard for electrical motors.
NEMA Insulation Classes
Electrical insulation systems rated by standard NEMA classifications to maximize allowable operating temperatures.
Nema Starters
Nema sized contactors or starters.