EN 1452 - Unplasticized Poly Vinyl Chloride (PVC-U) - Dimensions
Dimensions of PVC-U pipe according EN 1452.
Dimensions of PVC-U pipes according EN 1452 Plastics piping systems for water supply. Unplasticized poly (vinyl chloride) (PVC-U). Fitness for purpose of the system:
For full table with Table Z - rotate the screen!3
| Nominal Outside Diameter (mm) |
Min. Wall Thickness (mm) | |||||||
| S 20 SDR 41 |
S 16.7 SDR 34.4 |
S 16 SDR 33 |
S 12.5 SDR 26 |
S 10 SDR 21 |
S 8 SDR 17 |
S 6.3 SDR 13.6 |
S 5 SDR 11 |
|
| Nominal Pressure PN (design coefficient 2.5) | ||||||||
| PN 6 | PN 6 | PN 8 | PN 10 | PN 12.5 | PN 16 | PN 20 | ||
| 12 | 1.5 | |||||||
| 16 | 1.5 | |||||||
| 20 | 1.5 | 1.9 | ||||||
| 25 | 1.5 | 1.9 | 2.3 | |||||
| 32 | 1.5 | 1.6 | 1.9 | 2.4 | 2.9 | |||
| 40 | 1.5 | 1.6 | 1.9 | 2.4 | 3.0 | 3.7 | ||
| 50 | 1.6 | 2.0 | 2.4 | 3.0 | 3.7 | 4.6 | ||
| 63 | 2.0 | 2.5 | 3.0 | 3.8 | 4.7 | 5.8 | ||
| 75 | 2.3 | 2.9 | 3.6 | 4.5 | 5.6 | 6.8 | ||
| 90 | 2.8 | 3.5 | 4.3 | 5.4 | 6.7 | 8.2 | ||
| Nominal Pressure PN (design coefficient 2.0) | ||||||||
| PN 6.3 | PN 7.5 | PN 8 | PN 10 | PN 12.5 | PN 16 | PN 20 | PN 25 | |
| 63 | 2.0 | 2.0 | 2.4 | 3.0 | 3.8 | |||
| 75 | 2.0 | 2.2 | 2.9 | 3.6 | 4.5 | |||
| 90 | 2.0 | 2.7 | 3.5 | 4.3 | 5.4 | |||
| Nominal Pressure PN (design coefficient 2.0) | ||||||||
| PN 6 | PN 7.5 | Pn 8 | PN 10 | PN 12.5 | PN 16 | PN 20 | PN 25 | |
| 110 | 2.7 | 3.2 | 3.4 | 4.2 | 5.3 | 6.6 | 8.1 | 10.0 |
| 125 | 3.1 | 3.7 | 3.9 | 4.8 | 6.0 | 7.4 | 9.2 | 11.4 |
| 140 | 3.5 | 4.1 | 4.3 | 5.4 | 6.7 | 8.3 | 10.3 | 12.7 |
| 160 | 4.0 | 4.7 | 4.9 | 6.2 | 7.7 | 9.5 | 11.8 | 14.6 |
| 180 | 4.4 | 5.3 | 5.5 | 6.9 | 8.6 | 10.7 | 13.3 | 16.4 |
| 200 | 4.9 | 5.9 | 6.2 | 7.7 | 9.6 | 11.9 | 14.7 | 18.2 |
| 225 | 5.5 | 6.6 | 6.9 | 8.6 | 10.8 | 13.4 | 16.6 | |
| 250 | 6.2 | 7.3 | 7.7 | 9.6 | 11.9 | 14.8 | 18.4 | |
| 280 | 6.9 | 8.2 | 8.6 | 10.7 | 13.4 | 16.6 | 20.6 | |
| 315 | 7.7 | 9.2 | 9.7 | 12.1 | 15.0 | 18.7 | 23.2 | |
| 355 | 8.7 | 10.4 | 10.9 | 13.6 | 16.9 | 21.1 | 26.1 | |
| 400 | 9.8 | 11.7 | 12.3 | 45.3 | 19.1 | 23.7 | 29.4 | |
| 450 | 11.0 | 13.2 | 13.8 | 17.2 | 21.5 | 26.7 | 33.1 | |
| 500 | 12.3 | 14.6 | 15.3 | 19.1 | 23.9 | 29.7 | 36.8 | |
| 560 | 13.7 | 16.4 | 17.2 | 21.4 | 26.7 | |||
| 630 | 15.4 | 18.4 | 19.3 | 24.1 | 30.0 | |||
| 710 | 17.4 | 20.7 | 21.8 | 27.2 | ||||
| 800 | 19.6 | 23.3 | 24.5 | 30.6 | ||||
| 900 | 22.0 | 26.3 | 27.6 | |||||
| 1000 | 24.5 | 29.2 | 30.6 | |||||