Engineering ToolBox - Resources, Tools and Basic Information for Engineering and Design of Technical Applications!

Electrical Motors - Locked Rotor Design Code Letters

NEMA locked rotor indicating code letters for electrical motors.

NEMA - The National Electrical Manufacturer's Association - who sets the design standards for motors, has established a NEMA Code letter designation to classify motors by the ratio of locked rotor kVA per horsepower.

Electrical Motors - Locked Rotor Design Code Letters
NEMA
Code Letter
kVA/HP
with locked rotor
Approximate Mid-Range Value
A 0 - 3.14 1.6
B 3.15 - 3.55 3.3
C 3.55 - 3.99 3.8
D 4.0 - 4.49 4.3
E 4.5 - 4.99 4.7
F 5.0 - 5.59 5.3
G 5.6 - 6.29 5.9
H 6.3 - 7.09 6.7
J 7.1 - 7.99 7.5
K 8.0 - 8.99 8.5
L 9.0 - 9.99 9.5
M 10.0 - 11.19 10.6
N 11.2 - 12.49 11.8
P 12.5 - 13.99 13.2
R 14.0 - 15.99 15.0
S 16.0 - 17.99  
T 18.0 - 19.99  
U 20.0 - 22.39  
V 22.4 - and up  

The starting kVA required by a motor starting at full voltage is determined from the nameplate on the motor or from the manufacturer.

In general it is accepted that small motors requires higher starting kVA than larger motors. Standard 3 phase motors often have these locked rotor codes:

  • less than 1 hp: Locked Rotor Code L, 9.0 - 9.99 kVA
  • 1 1/2 to 2 hp: Locked Rotor Code L or M, 9.0 - 11.19 kVA
  • 3 hp : Locked Rotor Code K, 8.0 - 8.99 kVA
  • 5 hp : Locked Rotor Code J, 7.1 - 7.99 kVA
  • 7.5 to 10 hp : Locked Rotor Code H, 6.3 - 7.09 kVA
  • more than 15 hp : Locked Rotor Code G, 5.6 - 6.29 kVA
3D Engineering ToolBox - draw and model technical applications! 2D Engineering ToolBox - create and share online diagram drawing templates! Engineering ToolBox Apps - mobile online and offline engineering applications!

Unit Converter


















































9.19.10

.
Cookie Settings