Engineering ToolBox - Resources, Tools and Basic Information for Engineering and Design of Technical Applications!

Indoor Conditions - Summer or Winter

Recommended indoor design conditions summer or winter.

For full table with Winter Conditions - rotate the screen!

Indoor Conditions - Summer or Winter
ApplicationSummerWinter
ExtraCommercialWith HumidificationWithout Humidification
Dry Bulb TemperatureRelative HumidityDry Bulb TemperatureRelative HumidityDry Bulb TemperatureRelative HumidityDry Bulb Temperature
(oF)
(%)(oF)
(%)(oF)
(%)(oF)
General Comfort
Apartment, House, Hotel, Office, Hospital, School ..
74 - 76 50 - 45 77 - 79 50 - 54 74 - 76 35 - 30 75 - 77
Retail Shops for shorter terms occupancy
Bank, barber shop, beauty shop, department store, supermarket ..
76 - 78 50 - 45 78 - 80 50 - 45 72 - 74 35 - 30 73 - 75
High latent load and low sensible load applications
Auditoriums, churches, bars, restaurants, kitchens
76 - 78 55 - 50 78 - 80 65 - 50 72 - 74 40 - 35 74 - 76
Factories
Work shops, assembly areas, machining rooms ..
77 - 80 55 - 45 80 - 85 60 - 50 68 - 72 35 - 30 70 - 74
3D Engineering ToolBox - draw and model technical applications! 2D Engineering ToolBox - create and share online diagram drawing templates! Engineering ToolBox Apps - mobile online and offline engineering applications!

Unit Converter


















































9.19.10

.
Cookie Settings