Engineering ToolBox - Resources, Tools and Basic Information for Engineering and Design of Technical Applications!

Compressed Air - Size of Pipe vs. Capacity

Air pipe lines capacities at pressure 100 psi (6.9 bar).

Recommended air pipe line sizes with schedule 40 steel pipes and air pressure 100 psi (6.9 bar, 689500 Pa):

Compressed Air - Recommended Size of Pipe vs. Capacity

Free Air Flow
(cfm)
Recommended Pipe Size (inches)
Length of Pipe (feet)
255075100150200250
5 1/2 1/2 1/2 1/2 1/2 1/2 1/2
10 1/2 1/2 1/2 1/2 1/2 1/2 1/2
15 1/2 1/2 1/2 1/2 3/4 3/4 3/4
20 1/2 1/2 3/4 3/4 3/4 3/4 3/4
25 1/2 3/4 3/4 3/4 3/4 1 1
30 1/2 3/4 3/4 3/4 1 1 1
35 3/4 3/4 3/4 3/4 1 1 1
40 3/4 3/4 3/4 1 1 1 1
45 3/4 3/4 1 1 1 1 1 1/4
50 3/4 1 1 1 1 1 1/4 1 1/4
55 3/4 1 1 1 1 1/4 1 1/4 1 1/4
60 3/4 1 1 1 1 1/4 1 1/4 1 1/4
65 3/4 1 1 1 1 1/4 1 1/4 1 1/4
70 3/4 1 1 1 1/4 1 1/4 1 1/4 1 1/4
75 1 1 1 1 1/4 1 1/4 1 1/4 1 1/4
80 1 1 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4
85 1 1 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4
90 1 1 1 1/4 1 1/4 1 1/4 1 1/4 1 1/2
95 1 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/2
100 1 1 1/4 1 1/4 1 1/4 1 1/4 1 1/2 1 1/2
3D Engineering ToolBox - draw and model technical applications! 2D Engineering ToolBox - create and share online diagram drawing templates! Engineering ToolBox Apps - mobile online and offline engineering applications!

Unit Converter


















































9.19.10

.