Engineering ToolBox - Resources, Tools and Basic Information for Engineering and Design of Technical Applications!

Electrical Motors - Maximum Cable Size and Length vs. Power

Maximum electrical motor cable length vs. power.

Three phase 230 V electrical motors and maximum cable length with 3% calculated voltage drop.

Electrical Motors - Maximum Cable Size and Length vs. Power
Electric Motor PowerMaximum Cable Length (m, ft)
(kW)(hk)30 (98)50 (164)
100 (328)
Cable Size (mm2)
0.5 0.68 1.5 1.5 1.5
1 1.36 1.5 1.5 1.5
1.5 2.04 1.5 1.5 1.5
2 2.76 1.5 2.5 4
2.5 3.4 1.5 2.5 4
3 4.08 2.5 2.5 6
3.5 4.78 2.5 4 6
4 5.44 2.5 4 6
4.5 6.12 4 4 10
5 6.80 4 4 10
6 8.16 6 6 10
7 9.52 10 10 16
8 10.9 10 10 16
9 12.2 10 10 16
10 13.6 16 16 16
12 16.3 16 16 16
14 19.0 16 16 25
16 21.8 16 16 25
18 24.5 25 25 35
20 27.2 25 25 35
22 29.9 25 25 35
24 32.6 35 35 35
26 35.4 35 35 35
28 38.1 35 35 50
30 40.8 35 35 50
35 47.6 50 50 50
40 54.4 70 70 70
45 61.2 70 70 70
50 68 70 70 70
55 74.8 70 70 70
60 81.6 95 95 95
65 88.4 120 120 120
70 95.2 120 120 120
75 102 150 120 150
80 109 150 150 150
85 116 185 150 185
90 122 185 185 185
95 129 185 185 185
100 136 240 240 240
3D Engineering ToolBox - draw and model technical applications! 2D Engineering ToolBox - create and share online diagram drawing templates! Engineering ToolBox Apps - mobile online and offline engineering applications!

Unit Converter


















































9.19.10

.
Cookie Settings