Intermediate Metal Conduit - IMC
Intermediate Metal Conduit - IMC - dimensions:
Trade Size | Average Outside Diameter | Average Wall Thickness | Approx. Weight | ||||
---|---|---|---|---|---|---|---|
(in) | (mm) | (in) | (mm) | (in) | (mm) | (lbs/100 ft) | (kg/30 m) |
1/2 | 16 | 0.815 | 20.7 | 0.07 | 1.79 | 62 | 28 |
3/4 | 21 | 1.029 | 26.13 | 0.075 | 1.9 | 84 | 38 |
1 | 27 | 1.29 | 32.76 | 0.085 | 2.16 | 119 | 54 |
1 1/4 | 35 | 1.638 | 41.6 | 0.085 | 2.16 | 158 | 72 |
1 1/2 | 41 | 1.883 | 47.82 | 0.09 | 2.29 | 194 | 88 |
2 | 53 | 2.36 | 59.94 | 0.095 | 2.41 | 256 | 116 |
2 1/2 | 63 | 2.857 | 72.56 | 0.14 | 3.56 | 441 | 200 |
3 | 78 | 3.476 | 88.29 | 0.14 | 3.56 | 543 | 246 |
3 1/2 | 91 | 3.971 | 100.86 | 0.14 | 3.56 | 629 | 285 |
4 | 103 | 4.466 | 113.43 | 0.14 | 3.56 | 700 | 318 |
IMC is covered by Article 342 of the National Electric Code (NEC).
Related Topics
• Electrical
Electrical engineering with units, amps and electrical wiring. Wire gauges, electrical formulas, motors and more.
Related Documents
AWG - Wire Gauge Sizes: Current Ratings, Charts, Measurements, and Conversion Guide
Amp ratings vs. US AWG wire gauge.
AWG Wire Gauge Chart & Table – American Wire Gauge (AWG) Standards
The AWG (American Wire Gauge) wire size chart with detailed specifications on wire diameter, resistance, and ampacity. Find conversions between AWG sizes and metric units for electrical and engineering applications.
Electrical Metal Tubing (EMT) - Conduits
Trade sizes and max. distance between conduit supports.
Rigid Aluminum Conduits - RAC
Rigid Aluminum Conduits dimensions.