Gas Vent Termination - Clearance vs. Roof Slope
Roof Slope | Roof Degrees | Clearance (in) |
---|---|---|
flat to 6/12 | 27 | 12 |
6/12 - 7/12 | 27 - 30 | 15 |
7/12 - 8/12 | 30 - 34 | 18 |
8/12 - 9/12 | 34 - 37 | 24 |
9/12 - 10/12 | 37 - 40 | 30 |
10/12 - 11/12 | 40 - 43 | 39 |
11/12 - 12/12 | 43 - 45 | 48 |
Related Topics
• Gases and Compressed Air
Properties of air, LNG, LPG and other common gases. Pipeline capacities and sizing of relief valves.
• Ventilation Systems
Design of systems for ventilation and air handling - air change rates, ducts and pressure drops, charts and diagrams and more.
Related Documents
Air Supply to a Boiler House
Incomplete boiler combustion may generate carbon monoxide - CO - and re-ignition may cause disastrous effects on personnel and property.
Combustion of Fuels - Carbon Dioxide Emission
Environmental emission of carbon dioxide CO2 when combustion fuels like coal, oil, natural gas, LPG and bio energy.
Natural Gas - Equipment Consumption
Natural gas consumption for equipment like boiling pans, ovens, cookers, kettles and more.
Propane Gas Piping - Low Pressure Capacity vs. Size
Sizing of low pressure propane gas pipe lines - Imperial units.