Outdoor Supply Air Rates

Recommended supply air rates of outdoor air - with or without smoking - in rooms like banks, assembly halls, hotels and many more.

The rates of outdoor make-up or supply air in the table below can be used as a guideline in the design of ventilation systems.

Air Shifts

Air shift is the number of times the air in a room is replaced by supply air per hour and can be expressed as

n = q / V                    (1)

where

n = air shifts (1/h)

q = supply air to the room (m3 /h)

V = room volume (m3 )

Example - Air Shifts

The air supply to a room with volume 10 m 3 is 5 m3 /h . The air shifts can be calculated

n = ( 5 m3 /h ) / ( 10 m3 )

= 0.5 1/h

Recommended Supply Air to some typical Rooms

Outdoor Supply Air Rates

Type of Building and Room
Air Shifts
- n -
(1/h)
Supply Air flow
( l/s per m2
floor area)
Supply Air Flow
(l/s)
Animals Sheep 3 per animal
Horses 40 per animal
Hens 3 per animal
Cows 100 per animal
Chickens 2 per animal
Pigs, sow 60 per animal
Piglet 15 per animal
Apartments 15 per person
Assembly halls 5 - 10 10 - 15 per person
Auditoriums 10 - 15 per person
Bakeries Production 8
Pastry room 6
Banks Service 2 - 3
Archive 1
Staff 2 - 3
Baths 5 - 8 15
Barber Shops 10 - 15 per person
Bars 15 - 20 per person
Beauty Shops 10 - 15 per person
Bowling Alleys 10 - 15 per person
Cafeterias 4 10 - 15 per person
Cinemas/Theaters 5 - 10 7 - 10 per person
Chemist's shops Sterile room 15
Laboratory 15
Packing room 4
Store 1
Churches 2 10 per person
Clubhouses 15 - 20 per person
Cocktail Lounges 15 - 20 per person
Computer Rooms 10 - 15 per person
Court Houses 10 - 15 per person
Dance halls 15 - 20 per person
Dental Clinics, Offices 10 - 15 per person
Department Stores (cfm/Sq.Ft) 0.3
Dining Halls 10 - 15 per person
Drug Shop 10 - 15 per person
Engine rooms 4
Exhibition halls 10 - 20
Fire Stations 10 - 15 per person
Garages 5 - 6 > 1
Hospitals General 15 per person
Therapy 9
Operating theater 14
Autopsy 9
Hotels Reception 15 - 20 per person
Room 3
Industries Factory 10 - 20 per person
Carpenter work shop 2 - 5
Car repair shop 4
Car repair shop, exhaust outlet 60 - 80 per car
Mechanical work shop 3 - 4
Welding 12 - 15
Assembly 4 - 5
Jails 10 - 15 per person
Jewelry Shop 10 - 15 per person
Libraries 10 - 15 per person
Lift Shaft (Lift Car) 8 - 10
Lunch Rooms, Luncheonettes 10 - 15 per person
Municipal Buildings 10 - 15 per person
Museums 10 - 15 per person
Smithies

6 - 7

Kitchens Small 20 - 40
Large 10 - 20
< 7 m2 15
> 7 m2 20
Industrial in general 25 - 30
Gas ovens 550/m2outside wall
Electric ovens 300/m2outside wall
Grill table 400/m2outside wall
Frying pan 300
Boiling pan 100 l 100
Boiling pan 200 l 200
Coffee machine 60
Refrigerated cabinet 7 - 10
Cooling and freezer room 0.3 - 0.5
Store 2 - 4
Laundries 10 - 15
Lavatories 5 - 10 10
Night Clubs 15 - 25 per person
Malls 10 - 15 per person
Motels 15 - 20 per person
Offices Module 3 - 8 10 - 20 per person
Landscape 10 - 20 per person
Conference room 15 - 30 per person
Lecture room 10 - 20 per person
Dining hall 15 - 25 per person
Staff, changing clothes 8 - 12
Dining room 8 - 10
Resting room 15 per person
Police Stations 10 - 15 per person
Post Offices 10 - 15 per person
Precision Manufacturing 10 - 15 per person
Restaurants 5 - 10 10 10 - 15 per person
Retail Stores (cfm/Sq.Ft) 0.3
Schools Classroom 4 - 5 10 - 15 per person
Shops 10 - 15 per person
Shopping Centers 10 - 15 per person
Sports halls 3 - 4
Supermarkets 10 per person
Swimming pools 5 - 10
Taverns 10 - 15 per person
Town Halls 10 - 15 per person
  • 1 dm3 (liter)/s = 10-3 m3 /s = 3.6 m3 /h = 0.03532 ft3 /s = 2.1189 ft3 /min (cfm) = 13.200 Imp.gal (UK)/min = 15.852 gal (US)/min = 792 Imp. gal (UK)/h

Smoking or Not Smoking versus Recommended Supply Air

Smoking has a dramatic impact on required make up air ( Chartered Institution of Building Service Engineers , CIBSE Guide B2):

Outdoor Supply Air Rates vs. Smoking
Level of SmokingProportion of occupants that smoke
(%)
Supply Air
(liter/s person)
No smoking 0 8
Some smoking 25 16
Heavy smoking 45 24
Very heavy smoking 75 36

Recommended Residential Air Ventilation

Recommended outdoor air supply according ASHRAE 62.2:

Outdoor Supply Air Rates - Residential Air Ventilation
Air Flow (cfm)
Floor Area
(ft2)
Bedrooms
0 - 12 - 34 - 56 - 7> 7
< 1500 30 45 60 75 90
1501 - 3000 45 60 75 90 105
3001 - 4500 60 75 90 105 120
4501 - 6000 75 90 105 120 135
6001 - 7500 90 105 120 135 150
> 7500 105 120 135 150 165

Related Topics

  • Ventilation Systems

    Design of systems for ventilation and air handling - air change rates, ducts and pressure drops, charts and diagrams and more.

Related Documents

  • Air Change Rate

    Calculate air change rates - equations in imperial and SI units.
  • Air Change Rates in typical Rooms and Buildings

    Fresh air (make up air) rquirements - or recommended air change rates (ACH) for typical rooms and buildings like auditoriums, kitchens, churches and more.
  • Heat Recovery Efficiency

    Classification of heat recovery efficiencies - temperature efficiency, moisture efficiency and enthalpy efficiency - online heat exchanger efficiency calculator.
  • Outdoor Makeup Air

    Acceptable indoor air quality and required make up air.
  • Pollution Concentration in Rooms

    Concentration of a pollution in a limited space as a room depends on the amount of polluted material spread in the room, supply of fresh air, outlets positions and construction, principles used for supply and outlet from the space.

Search

Search is the most efficient way to navigate the Engineering ToolBox.

Engineering ToolBox - SketchUp Extension - Online 3D modeling!

3D Engineering ToolBox Extension to SketchUp - add parametric components to your SketchUp model

Add standard and customized parametric components - like flange beams, lumbers, piping, stairs and more - to your Sketchup model with the Engineering ToolBox - SketchUp Extension - enabled for use with older versions of the amazing SketchUp Make and the newer "up to date" SketchUp Pro . Add the Engineering ToolBox extension to your SketchUp Make/Pro from the Extension Warehouse !

Translate this Page

Translate this page to Your Own Language .

About the Engineering ToolBox!

Privacy Policy

We don't collect information from our users. More about

We use a third-party to provide monetization technologies for our site. You can review their privacy and cookie policy here.

You can change your privacy settings by clicking the following button: .

Citation

This page can be cited as

  • The Engineering ToolBox (2003). Outdoor Supply Air Rates. [online] Available at: https://www.engineeringtoolbox.com/ventilation-air-flow-rate-d_115.html [Accessed Day Month Year].

Modify the access date according your visit.

3D Engineering ToolBox - draw and model technical applications! 2D Engineering ToolBox - create and share online diagram drawing templates! Engineering ToolBox Apps - mobile online and offline engineering applications!

Unit Converter

















































5.8.12

.