Outdoor Temperatures and Relative Humidity - U.S. Winter and Summer Conditions
Outdoor summer and winter design temperatures and relative humidity for U.S. states and cities.
The table below indicates the summer and winter design conditions in U.S. states and cities.
For full table with Summer Condtions - rotate the screen!
| State | City | January | July | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Average Daily Temperature (oF) | Design Dry Bulb Temperature (oF) | Normal Relative Humidity (%) | Average Daily Temperature (oF) | Design Dry Bulb Temperature (oF) | Normal Relative Humidity (%) | ||||||
| 7:30 am. | 1:30 pm. | 7:30 pm. | 7:30 am. | 1:30 pm. | 7:30 pm. | ||||||
| Alabama | Birmingham | 10 | 81 | 61 | 66 | 95 | 84 | 56 | 68 | ||
| Mobile | 52.5 | 10 | 81.5 | 95 | 90 | 64 | 78 | ||||
| Arizona | Flagstaff | -10 | 83 | 58 | 90 | 77 | 36 | ||||
| Phoenix | 53.9 | 25 | 75 | 47 | 39 | 89.6 | 105 | 53 | 31 | 23 | |
| Yuma | 30 | 56 | 37 | 27 | 110 | 51 | 31 | 23 | |||
| Arkansas | Little Rock | 42.4 | 5 | 80 | 67 | 68 | 80.5 | 95 | 85 | 55 | 59 |
| California | Eureka | 30 | 87 | 77 | 90 | 92 | 80 | ||||
| Fresno | 25 | 93 | 80 | 66 | 105 | 61 | 36 | 20 | |||
| Los Angeles | 52.1 | 35 | 63 | 46 | 51 | 68.3 | 90 | 85 | 50 | 54 | |
| Sacramento | 30 | 90 | 82 | 70 | 100 | 76 | 46 | 28 | |||
| San Diego | 35 | 76 | 58 | 60 | 85 | 86 | 68 | 65 | |||
| San Francisco | 35 | 84 | 69 | 70 | 85 | 92 | 75 | 78 | |||
| Colorado | Denver | 31.9 | -10 | 54 | 37 | 41 | 70.6 | 95 | 55 | 27 | 30 |
| Grand Junction | -15 | 77 | 64 | 64 | 95 | 48 | 27 | 22 | |||
| Pueblo | -20 | 67 | 44 | 48 | 95 | 73 | 34 | 35 | |||
| Connecticut | New Haven | 0 | 75 | 65 | 69 | 95 | 77 | 64 | 74 | ||
| Delaware | Wilmington | 33.3 | 0 | 77 | 62 | 70 | 74.0 | 95 | 80 | 52 | 69 |
| District of Columbia | Washington | 37.2 | 0 | 73 | 56 | 64 | 77.0 | 95 | 78 | 52 | 64 |
| Florida | Jacksonville | 25 | 89 | 56 | 75 | 95 | 85 | 57 | 76 | ||
| Miami | 67.8 | 35 | 87 | 59 | 75 | 82.0 | 91 | 83 | 64 | 76 | |
| Georgia | Atlanta | 43.8 | 10 | 80 | 64 | 69 | 77.5 | 95 | 83 | 57 | 68 |
| Augusta | 10 | 84 | 59 | 69 | 98 | 83 | 55 | 69 | |||
| Savannah | 20 | 83 | 58 | 72 | 95 | 85 | 61 | 80 | |||
| Idaho | Boise | 32.7 | -10 | 82 | 75 | 74 | 70.8 | 95 | 54 | 34 | 23 |
| Lewiston | -5 | 79 | 73 | 71 | 95 | 64 | 37 | 25 | |||
| Illinois | Cairo | 0 | 81 | 69 | 98 | 83 | 57 | ||||
| Chicago | 25.0 | -10 | 81 | 70 | 75 | 71.2 | 95 | 78 | 51 | 55 | |
| Peoria | -10 | 73 | 72 | 77 | 96 | 81 | 53 | 58 | |||
| Indiana | Fort Wayne | -10 | 84 | 75 | 81 | 95 | 84 | 53 | 58 | ||
| Indianapolis | 29.1 | -10 | 83 | 72 | 78 | 73.4 | 95 | 84 | 54 | 60 | |
| Terre Haute | 0 | 82 | 70 | 76 | 95 | 77 | 50 | 56 | |||
| Iowa | Davenport | -15 | 95 | ||||||||
| Sioux City | -20 | 78 | 67 | 72 | 95 | 86 | 55 | 54 | |||
| Kansas | Dodge City | -10 | 78 | 57 | 61 | 95 | 77 | 45 | 52 | ||
| Topeka | -10 | 78 | 64 | 67 | 100 | 85 | 54 | 54 | |||
| Kentucky | Louisville | 35.2 | 0 | 78 | 68 | 69 | 75.9 | 95 | 77 | 52 | 57 |
| Louisiana | New Orleans | 53.9 | 20 | 85 | 67 | 73 | 81.3 | 95 | 84 | 64 | 72 |
| Shreveport | 20 | 83 | 67 | 66 | 100 | 86 | 56 | 62 | |||
| Maine | Portland | 23.4 | -5 | 81 | 65 | 74 | 65.6 | 90 | 78 | 58 | 76 |
| Maryland | Baltimore | 34.6 | 0 | 72 | 68 | 56 | 74.8 | 95 | 71 | 52 | 65 |
| Massachusetts | Boston | 31.3 | 0 | 72 | 59 | 67 | 71.1 | 92 | 72 | 55 | 70 |
| Michigan | Detroit | 25.9 | -10 | 82 | 71 | 77 | 70.0 | 95 | 74 | 50 | 56 |
| Grand Rapids | -10 | 85 | 78 | 80 | 95 | 76 | 51 | 54 | |||
| Minnesota | Duluth | -25 | 78 | 74 | 74 | 93 | 87 | 61 | 66 | ||
| Minneapolis | 16.0 | -20 | 82 | 72 | 75 | 70.6 | 95 | 82 | 54 | 54 | |
| Mississippi | Vicksburg | 10 | 82 | 65 | 67 | 95 | 87 | 61 | 70 | ||
| Missouri | Kansas City | -10 | 78 | 64 | 66 | 100 | 76 | 48 | 47 | ||
| St. Louis | 32.3 | 0 | 77 | 65 | 68 | 76.9 | 95 | 73 | 50 | 55 | |
| Montana | Billings | -25 | 67 | 73 | 60 | 90 | 65 | 40 | 33 | ||
| Butte | -20 | 76 | 70 | 71 | 95 | 82 | 36 | 33 | |||
| Nebraska | North Platte | -20 | 80 | 62 | 66 | 85 | 84 | 50 | 46 | ||
| Omaha | 24.9 | -10 | 82 | 68 | 73 | 75.3 | 65 | 80 | 51 | 51 | |
| Nevada | Reno | 34.0 | -5 | 82 | 67 | 54 | 66.2 | 95 | 72 | 25 | 20 |
| New Hampshire | Concord | 22.2 | -15 | 78 | 60 | 69 | 67.1 | 90 | 80 | 49 | 69 |
| New Jersey | Atlantic City | 33.6 | 5 | 79 | 68 | 74 | 72.2 | 95 | 81 | 72 | 82 |
| Newark | 0 | 72 | 79 | 65 | 95 | 75 | 51 | 65 | |||
| Trenton | 0 | 73 | 62 | 68 | 95 | 77 | 55 | 68 | |||
| New Mexico | Albuquerque | 36.6 | 0 | 68 | 51 | 46 | 76.4 | 95 | 59 | 33 | 28 |
| New York | Albany | -10 | 75 | 63 | 71 | 93 | 79 | 52 | 64 | ||
| Buffalo | -5 | 79 | 72 | 78 | 93 | 78 | 53 | 63 | |||
| New York | 33.8 | 0 | 72 | 61 | 66 | 74.5 | 95 | 75 | 58 | 68 | |
| Rochester | -5 | 81 | 73 | 79 | 95 | 80 | 50 | 60 | |||
| North Carolina | Asheville | 0 | 82 | 59 | 69 | 93 | 88 | 56 | 73 | ||
| Raleigh | 41.1 | 10 | 82 | 57 | 69 | 76.2 | 95 | 86 | 55 | 72 | |
| North Dakota | Bismarck | 12.2 | -30 | 77 | 71 | 75 | 67.8 | 95 | 85 | 52 | 49 |
| Ohio | Cincinnati | 0 | 82 | 70 | 74 | 95 | 84 | 52 | 60 | ||
| Cleveland | 28.0 | 0 | 81 | 72 | 79 | 69.8 | 95 | 79 | 52 | 58 | |
| Columbus | -10 | 83 | 71 | 76 | 95 | 78 | 52 | 60 | |||
| Toledo | -10 | 79 | 72 | 75 | 95 | 76 | 52 | 59 | |||
| Oklahoma | Oklahoma City | 38.9 | 0 | 79 | 62 | 65 | 80.0 | 101 | 80 | 49 | 51 |
| Oregon | Baker | -5 | 83 | 81 | 78 | 90 | 69 | 68 | 36 | ||
| Portland | 41.0 | 10 | 87 | 82 | 78 | 63.8 | 90 | 86 | 63 | 48 | |
| Pennsylvania | Harrisburg | 0 | 72 | 49 | 65 | 95 | 78 | 51 | 62 | ||
| Philadelphia | 0 | 74 | 65 | 68 | 95 | 78 | 52 | 65 | |||
| Pittsburgh | 29.0 | 0 | 77 | 67 | 63 | 70.2 | 95 | 80 | 52 | 63 | |
| Scranton | -5 | 80 | 67 | 95 | 77 | 50 | |||||
| Rhode Island | Providence | 29.9 | 0 | 73 | 60 | 67 | 70.1 | 93 | 79 | 57 | 73 |
| South Carolina | Charleston | 15 | 87 | 55 | 76 | 95 | 88 | 64 | 82 | ||
| Columbia | 46.2 | 10 | 81 | 57 | 65 | 79.6 | 95 | 83 | 56 | 68 | |
| South Dakota | Huron | -20 | 79 | 72 | 76 | 95 | 86 | 52 | 49 | ||
| Rapid City | -20 | 71 | 69 | 67 | 95 | 71 | 42 | 40 | |||
| Tennessee | Knoxville | 0 | 83 | 65 | 69 | 95 | 83 | 55 | 66 | ||
| Memphis | 0 | 82 | 67 | 73 | 95 | 85 | 55 | 59 | |||
| Texas | Amarillo | -10 | 71 | 51 | 52 | 100 | 77 | 43 | 42 | ||
| Corpus Christi | 20 | 88 | 66 | 75 | 95 | 93 | 58 | 68 | |||
| Dallas | 10 | 81 | 62 | 62 | 100 | 79 | 50 | 47 | |||
| El Paso | 10 | 63 | 45 | 39 | 100 | 60 | 37 | 30 | |||
| Houston | 53.3 | 20 | 85 | 66 | 73 | 82.1 | 95 | 90 | 58 | 66 | |
| San Antonio | 20 | 82 | 60 | 59 | 100 | 88 | 49 | 45 | |||
| Utah | Salt Lake City | 31.0 | -10 | 80 | 71 | 72 | 73.5 | 95 | 56 | 27 | 23 |
| Vermont | Burlington | 19.1 | -10 | 81 | 69 | 78 | 67.3 | 90 | 76 | 54 | 67 |
| Virginia | Richmond | 38.5 | 15 | 84 | 60 | 68 | 76.0 | 95 | 81 | 57 | 72 |
| Washington | Seattle | 41.0 | 15 | 86 | 80 | 74 | 63.0 | 85 | 86 | 63 | 47 |
| Walla Walla | -5 | 80 | 74 | 78 | 95 | 50 | 33 | 22 | |||
| West Virginia | Charleston | 35.1 | 0 | 79 | 64 | 70 | 73.0 | 95 | 88 | 53 | 67 |
| Parkersburg | -10 | 82 | 66 | 74 | 95 | 80 | 52 | 65 | |||
| Wisconsin | Green Bay | -15 | 75 | 68 | 73 | 95 | 85 | 58 | 64 | ||
| Milwaukee | 22.3 | -15 | 76 | 70 | 73 | 68.2 | 95 | 81 | 58 | 64 | |
| Wyoming | Cheyenne | 28.2 | -15 | 59 | 48 | 55 | 65.9 | 95 | 73 | 36 | 40 |