Absorbed Solar Radiation
Solar radiation absorbed by various materials.
Absorbed Solar Radiation by Surface Color
Solar energy absorbed depends on surface color:
Surface Color | Absorb Factor Fraction of Incident Radiation Absorbed (approximated) |
---|---|
White smooth surfaces | 0.25 - 0.40 |
Grey to dark grey | 0.40 - 0.50 |
Green, red and brown | 0.50 - 0.70 |
Dark brown to blue | 0.70 - 0.80 |
Dark blue to black | 0.80 - 0.90 |
Absorbed Solar Radiation by Material
Substance | Absorb Factor Fraction of Incident Radiation Absorbed |
---|---|
Aluminum, polished | 0.30 |
Aluminum paint | 0.20 |
Aluminum, anodized | 0.15 |
Brick, glazed | 0.35 |
Brick, common light red | 0.55 |
Brick, common red | 0.68 |
Brick, wire cut red | 0.52 |
Brick, blue | 0.89 |
Cork | 0.45 |
Limestone, light | 0.35 |
Limestone, dark | 0.50 |
Linoleum, red-brown | 0.84 |
Sandstone, light grey | 0.62 |
Sandstone, red | 0.73 |
Marble, white | 0.44 |
Soft rubber, gray | 0.65 |
Marble, dark | 0.66 |
Granite, reddish | 0.55 |
Magnesium oxide, evaporated | 0.08 |
Graphite | 0.84 |
Porcelain | 0.50 |
Steel, vitreous enameled green | 0.76 |
Steel, vitreous enameled dark red | 0.81 |
Steel, vitreous enameled blue | 0.80 |
Iron, galvanized new | 0.64 |
Iron, galvanized dirty | 0.92 |
Iron, galvanized white washed | 0.22 |
Concrete | 0.60 |
Copper, polished | 0.18 |
Copper, tarnished | 0.64 |
Lead, old | 0.79 |
Asbestos cement, roof tiles old | 0.83 |
Asbestos cement, roof tiles red | 0.69 |
Asbestos slate | 0.81 |
Asphalt roofing, new | 0.91 |
Asphalt roofing, old | 0.82 |
Bitumen-covered roofing sheet, brown | 0.87 |
Slate, blue grey | 0.87 |
Tile, clay red | 0.64 |
Tile, concrete uncolored | 0.65 |
Tile, concrete black | 0.91 |
Vitreous enamel, white | 0.39 |
White Dutch tile | 0.18 |
Related Topics
-
Thermodynamics
Work, heat and energy systems.
Related Documents
-
Building Materials - Radiation Constants
The radiation constant is the product between the Stefan-Boltzmann constant and the emissivity constant for a material. -
Electromagnetic Spectrum
The electromagnetic spectrum with wavelengths and frequencies. -
Glazing Materials - Optical Properties
Optical properties of commonly used glazing materials. -
Illuminance - Recommended Light Levels
Working activities and light levels - required illuminance. -
LENI - Lighting Energy Numeric Indicator
Energy consumption of lighting systems -
Materials - Light Reflecting Factors
Light reflecting factor materials. -
Optical Distance Law
Geometric dilution of light vs. distance. -
Radiation - Surfaces Emissivity Coefficients
Radiation emissivity of common materials like water, ice, snow, grass and more. -
Radiation Heat Transfer
Heat transfer due to emission of electromagnetic waves is known as thermal radiation. -
Refractive Index common Liquids, Solids and Gases
Some common fluids and their refractive index. -
Solar Heat Transmission through Windows
Solar heat gain through windows with roller shades, vertical blinds and Venetian blinds -
Solar Radiation - Daily Surface Energy
Daily surface energy from solar radiation. -
Solar Radiation through Windows
Heat from sun transmitted through windows. -
Sun Charts
Online solar chart creator. -
Surface Emissivity Coefficients
The radiation heat transfer emissivity coefficients for some common materials like aluminum, brass, glass and many more. -
Surface Radiation Absorptivity
Radiation surface absorptivity.