Electrical Motors - Single Phase 230 V Circuit Wiring
Copper wire gage and transformer size for single phase 230 volts electrical motors.
All wiring and electrical connections should comply with the National Electrical Code (NEC) and local codes and practices.
Recommended copper wire gage and transformer size for single phase 230 Volts electrical motors:
Motor Power (hp) | Transformer Apparent Power (kVA) | Wire Gauge (AWG) | ||||
---|---|---|---|---|---|---|
Distance from Motor to Transformer (feet) | ||||||
100 | 150 | 200 | 300 | 500 | ||
1.5 | 3 | 10 | 8 | 8 | 6 | 4 |
2 | 3 | 10 | 8 | 8 | 8 | 4 |
3 | 5 | 8 | 8 | 8 | 4 | 2 |
5 | 7.5 | 6 | 4 | 4 | 2 | 0 |
7.5 | 10 | 6 | 4 | 3 | 1 | 0 |
With undersized wire between motor and power source the starting and load carrying capabilities of the motor will be limited.
Apparent Power is the power supplied to the electric circuit - typical from a power supplier to the grid - to cover the real and reactive power consumption in the loads.
Related Topics
-
Electrical
Electrical engineering with units, amps and electrical wiring. Wire gauges, electrical formulas, motors and more.
Related Documents
-
AWG - American Wire Gauge Converting Chart
American Wire Gauge (AWG) vs. cross sectional area converter. -
AWG - American Wire Gauge Current Ratings
Amp ratings vs. US AWG wire gauges. -
Electric Circuit Diagram - Drawing Template
Online shareable electric circuit diagram. -
Electric Motors - 230 & 460V Three Phase Circuits Wiring
Sizing of copper wire and transformers for three phase 230 & 460V electrical motors.